Wastewater treatment plant faults and emergency service

Most faults in a domestic wastewater treatment plant (WWTP) are caused by a lack of air, too much sludge or something that does not belong in the drains. Here you will find the most common symptoms, their causes and what you can do straight away. If you are not sure what to do, call us.

Safety first
Never climb into the plant or lean into it. Gases from wastewater, especially hydrogen sulphide, can quickly cause loss of consciousness. Disconnect the power supply before handling the blower or anything electrical.

Odour? We find the cause
On this page

Symptoms, causes and what to do

SymptomMost common causeWhat to do straight awayWhen to call us
Odour near the WWTP or from the drains, often a smell of rotten eggsLack of oxygen: the blower is not running, is getting weaker or has a clogged filter, or the aeration diffusers are clogged. Too much sludge.Check that the blower is running and that air is bubbling evenly through the WWTP. Clean the blower filter.If the odour lasts more than 2–3 days or the blower is not running.
Blower not runningA tripped circuit breaker or residual current device (RCD), an interrupted power supply, a torn diaphragm (blower membrane). Many diaphragm blowers have a safety switch that turns them off when a diaphragm is damaged.Check the circuit breaker, the RCD and the socket. Do not take the blower apart.Straight away. Without air, treatment stops and the plant starts to smell.
Blower louder than usual or vibratingWorn diaphragms or valves, a clogged filter, loose mounting.Clean the filter and check that the blower stands level and does not touch the walls of its cabinet.If the sound changes noticeably. Replacing the diaphragms is cheaper than a new blower.
Cloudy or grey effluentToo much sludge, hydraulic overload (rainwater in the drains, a lot of laundry at once), incorrectly set recirculation.Spread laundry and baths over several days. Check that no rainwater is flowing into the WWTP.If the cloudiness lasts longer than a week or a sampling date is coming up.
Thick foam on the surfaceA new WWTP still becoming established, too much laundry detergent and cleaning products, overloading.In a new WWTP, foam is normal in the first few weeks. Otherwise, cut down on chemicals.If the foam overflows the tank or does not go away for a long time.
Sludge floating on the surface in the settling zoneThe WWTP has not been desludged for a long time, the surface skimmer is not working, the sludge is decomposing and gas is lifting it up.Do not add any chemicals.The recirculation needs adjusting and the plant needs desludging. Call us.
Higher water level in the WWTP, water draining slowly in the houseA blocked outlet or soakaway, a high water table, a pump fault in the pumping chamber.Use as little water as possible. If you have a pumping chamber, check the pump.Straight away, as the drains could back up.
Alarm on the control unitDepends on the WWTP type: blower failure, high water level, dosing fault.Note down the code or take a photo of the display.Straight away.

What does not belong in a treatment plant

Many faults start in the kitchen and bathroom, not in the treatment plant:

  • fats and oils from frying pans and deep fryers
  • wet wipes, sanitary products, cotton buds
  • medicines and antibiotics
  • paints, thinners, engine oil
  • large amounts of chlorine-based and aggressive cleaning products
  • food leftovers, coffee grounds, sand

Read more in our article →

Emergency service

If you have a fault, call +421 905 229 394. If you can, send us a photo or a short video of the plant and the blower. We can often advise you remotely straight away.

Every fault, repair and exceptional event must be recorded in the operating log (prevádzkový denník) under Government Regulation No. 269/2010 Coll. After a repair, we make the entry for you.

Spare parts

In our online shop ekotovar.sk (in Slovak), blower diaphragms cost from €37.50, service kits from €63.50 and new blowers from €195 (prices as of 6 November 2026). More →

Frequently asked questions

Will bacteria help with the smell?

If the cause is a lack of oxygen, bacteria will not help. First the air supply has to be restored and, if necessary, the plant desludged. Bacterial additives make sense, for example, after a chemical shock or while the plant is becoming established. More →

Can I switch the blower off at night?

No, unless the operating manual (prevádzkový poriadok) of your WWTP explicitly allows it. Most domestic treatment plants need air continuously, and some types run in cycles controlled by their own control unit.

What should I do during a power cut?

A short power cut will not harm the plant. When the power comes back on, check that the blower is running again. During a longer power cut, use as little water as possible. More →

Why choose Bednár Montáže

  • Certified inspection technicianInspections are carried out by Daniel Bednár, who is on the Slovak University of Technology (STU) list of inspection technicians.
  • Service after the warranty, tooWe look after your plant for years after start-up.
  • Paperwork in orderA report and an operating log entry after every visit.
  • Parts from our own online shopAir blowers, diaphragms and additives, average delivery 2.6 days.
  • All of SlovakiaWestern Slovakia regularly, elsewhere by agreement. Advice also online via WhatsApp.
  • Since 200026 years of experience with wastewater treatment plants.

Report a fault

Call +421 905 229 394 or fill in the form with a description of the problem.